pH-Cl-F P Control Unit
Control and regulating system for free chlorine and pH, made of eSELECT-M2 controller, block valves, connection for tube 10×14 mm, water
filter with washable net cartridge 150 microns, methacrylate probe holder with proximity switch and adjustment flow system, manual sampling,
free inorganic and organic chlorine probe, (0 – 20) ppm measuring range, probe shows low pH dependence (pH working range 4-12 pH), chlorine
measuring is not affected by isocyanuric acid, surfactants/flocculants presence, the probe is automatic temperature-compensated, 0,7 mt
probe cable, pH electrode with plastic body with cable 1 mt (Tmax=60° C Pmax=6 bar) working range 0÷14 pH, 3 buffer solution 55ml bottles
(pH 4, 7 and 9), 2 manual pumps wiring connection available in the central box trunking. The unit required a constant flow rate between 30 and
40l/h, do not exceed the maximum operating pressure of 1 bar (free discharge at probe holder outlet) while water temperature cannot overcome
45°C. The probe has integrated temperature compensation. Suitable for software EtaCloud connection; optional accessory: connectivity kit.
Panel dimensions 400 x 600 x 0.80 mm